6KLP23F25X9B1

Series: AF-60 LP - Micro Drives Brand: General Electric
Price
$1,073.00 CAD
Stock
14 In Stock

  • Input Voltage - 230 V, 50/60 Hz
  • Input Phase - 3-Phase
  • HP Rating - 1/4 HP
  • Factory Installed Options - Keypad
  • Enclosure Type - IP20/Open
  • Version - Future Version

Specifications

Environmental Conditions

Enclosure

  • IP20 (IP21 with optional kit)

Installation Location

  • For use at altitudes of (1000 m) or Less without derating

Ambient Temperature

  • -10° to +50° C for above 45° C, there will be derating: please consult GE

Ambient Humidity

  • 5 to 95 % Relative Humidity, Non-Condensing

Vibration

  • 1.0 G

Storage Temperatures

  • -25° to 65° C

Approvals & Certifications

  • CE
  • UL
  • cUL
  • C-Tick
  • WEEE
  • RoHS
  • Suitable for use on a Circuit capable of delivering not more than 100,000 RMS symmetrical amperes for 230 V and 400 V

Input Power Supply

Rated Input AC Voltage

  • 200-240 Vac, 1-Phase, 50/60 Hz, ± 10 % V
  • 200-240 Vac, 3-Phase, 50/60 Hz, ± 10 % V
  • 380-480 Vac, 3-Phase, 50/60 Hz, ± 10 % V

Maximum Voltage Imbalance

  • 3 % of rated Supply Voltage

True Power Factor

  • > 0.4 Nominal at Rated Load

Displacement Power Factor

  • r > 0.98

Switching on Input Power Supply

  • Maximum twice/minute

Environment According to EN60664-1

  • Overvoltage Category III/Pollution Degree 2

Output

Rated Output Voltage

  • 0 to 100 % of Supply Voltage

Output Frequency

  • 0 to 200 Hz (Adv. Vector Control Plus Mode),
  • 0 to 400 Hz (Volts/Hertz Mode)

Switching on Output

  • Unlimited

Acceleration / Deceleration Time

  • 0.05-3600 seconds

Overload Current Rating

  • 150 % of drive rated Current for 1 minute

Control

Control Method

  • Sinusoidal PWM Control (V/Hz with torque vector Control)

Switching Frequency Select (kHz)

  • 8
  • 12
  • 16
  • 4
  • 2

Operation Method

  • Keypad Operation: Hand, Off, Auto
  • Digital Input: Programmable for Start/Stop, Forward/Reverse, Jog
  • Timer Operation: Stop after predetermined time frame
  • Link Operation: RS-485 Modbus RTU

Frequency Reference Setting

  • Up or Down Buttons on keypad or external reference

Analog Input

  • Built in Potentiometer
  • 4-20 mA analogue Input
  • 0-10 Vdc Analog Input

Preset Speeds

  • 8 presets via Digital Inputs

Link Operation

  • Drive RS-485
  • Modbus RTU

Second Reference Setting

  • Switch from speed reference 1 to reference 2 via Digital Input

Trim Reference Setting

  • Available for speed reference offset via potentio meter, Voltage Input, or Current Input

Acceleration / Deceleration Time

  • 0.05-3600 seconds (Two acceleration and deceleration rates are selectable via digital inputs. Acceleration and deceleration patterns can be selected from linear or S-Curve

DC Injection Braking

  • Starting frequency: 0.0-400 Hz
  • Braking level: 0-150 % of rated Current
  • Braking Time: 0.0-60.0 seconds

Frequency Limit

  • 0 to 400 Hz

Jump Frequency Control

  • Two jump (or skip) frequencies via Parameter set to avoid mechanical vibration

Jogging Operation

  • Operation via on Key or Digital Input (Forward or Reverse)

Auto-Restart After Power Failure

  • Restarts the drive without stopping after instantaneous Power failure

Slip Compensation

  • Maintains motor at constant speed with load fluctuations

Energy Savings

  • Controls output voltage to minimize motor loss during constant speed operation

Start Mode Function

  • This functionality smoothly catches a Spinning motor

Logic Controller (LC)

Logic Controller Events

  • Over 23 Types of Programmable events

Comparators

  • Array of 4 Comparators

Timers

  • Array of 3 timers, Adjustable from 0.0 to 3600 sec

Logic Rules

  • Array of 4 boolean logic rules

Logic Controller States

  • Array of 20 logic Controller action States

Process Controller (PID)

Feedback Select

  • No function, analogue Input 1, analogue Input 2, pulse Input, local bus reference

Anti Windup

  • Disabled
  • Enabled

Start Speed

  • 0.0-200 Hz

Proportional Gain

  • 0.00-10.00

Integral Gain

  • 0.10-9999 seconds

Feed Forward Factor

  • 0 to 400 %

On Reference Bandwidth

  • 0 to 200 %

Indication

LEDs

  • Red - Indicates an Alarm
  • Yellow - Indicates a Warning
  • Green - Drive is On

Monitor Units Available

  • Frequency
  • Current
  • Voltage
  • Power
  • Horsepower
  • % Load
  • Speed
  • Time

Monitoring Parameters Available

Power

  • kW

Motor Voltage

  • V

Frequency

  • Hz

Motor Current

  • A

Motor Thermal

  • %

DC Link Voltage

  • V

Drive Current

  • A

Drive Maximum Current

  • A

Logic Controller State

  • ON / OFF

Documentation