AP6380 Input Isolated, Field Configurable Isolator

Brand: Eurotherm

The field configurable AP6380 signal conditioner offers wide ranging input capability for scaling, converting or isolating AC inputs ranging from 5 mA AC to 100 mA AC or 50 mV AC to 200 Vac.

The DC output of the AP6380 is proportional to the average of the fully-rectified AC input signal, and is calibrated for sine waves from DC to 1 KHz.

For current inputs above 100 mA AC, it is recommended that an input shunt resistor be used and the AP6380 be configured for the proper input voltage range.

For example, for a 5 A AC current transformer output, use the Action model C006 resistor (0.1 W, 5 W, 1%) and set the input for 0 to 500 mV AC.
Features
  • Field configurable input ranges: 50 mV to 200 Vac, 5 mA to 100 mA AC
  • Four field configurable output ranges: 0 to 5 V, 0 to 10 V, 0 to 1 mA, 4 to 20 mA
  • Eliminates ground loops
  • Plug-in installation
  • Selectable 120/240 Vac input power

1 model matching criteria
  • Coating - Without
  • Factory Calibration - Without
9 In Stock
$2,462.00CAD
Does not ship to Ohio, United States

Specifications

Brand

Accuracy

  • ± 0.1 % of Span Typical
  • ± 0.5 % of Span, Max.

Approvals & Certifications

  • CSA C22.2, No. M1982 (File No. LR42272-38)
  • UL (C,US), UL 508 (File No. E150323)

Consumption

  • Power Consumption: 3 W Typical
  • Power Consumption: 5 W, Max.

Display

  • LED Display

Electrical Connectors

  • 8-Pin

Frequency

  • Input Frequency: DC-1 kHz, Factory Calibrated at 60 Hz

Humidity

  • 10 to 95 % Relative Humidity, Non-Condensing at 45° C (113° F)

Hysteresis

  • ± 0.1 % of Span Typical
  • ± 0.5 % of Span, Max.

Input

  • 50 mV-200 Vac
  • 5-100 mA AC
  • Common Mode Voltage: 1,500 Vdc, Input to Ground
  • Input Overload (without Damage): 200 mA AC, 60 V Peak
  • Input Overload (without Damage): 300 Vac

Input Impedance

  • Current: 20 ohms, Typical
  • Voltage: > 100 kiloohms

Isolation

  • Input to Output to Power: 1,500 Vdc or Peak AC

Linearity

  • ± 0.1 % of Span Typical
  • ± 0.5 % of Span, Max.

Mounting

  • DIN Rail
  • Track/Surface

Operating Temperature

  • 0° to 60° C (32° to 140° F)

Output

  • 0-10 Vdc
  • 0-20 mA DC
  • Output Drive (Voltage): 10 mA - Max.
  • Output Drive: 20 Vdc Compliance (1 kiloohms, Max.

Output Impedence

  • Output Source Impedance (Current): > 100 kiloohms
  • Output Source Impedance (Voltage): < 10 ohms

Power

  • Selectable 120/240 Vac (± 10 %, 50/60 Hz)

Response Time

  • 250 milliseconds Typical

Span & Zero Adjustments

  • Span Turn Down, Zero Turn Up: 50 % of Full Scale

Stability

  • ± 0.025 % of Full Scale/°C Typical

Storage Temperature

  • -15° to 70° C (5° to 158° F)
show more