EPower is fitted with a 4 line x 10 character display with indication of the process values, and diagnostic information, along with an alarm and event message center.

Optionally, the EPower has a 32h8e remote display to allow for the process values and alarm information to be presented front of panel in a clear and unambiguous way.

Secure access to the local setpoint is also provided to allow for local control when needed.

The remote display, as an indicator, can also provide over temperature policeman functionality removing the need.
Features
  • Fully software configurable
  • Predictive load management
  • Current rating 50 to 630 A (Nominal load 16 to 630 A)
  • Voltage up to 690 Vac
  • All types of firing modes
  • Measurement accuracy <1%
  • Large integral four row display
  • Remote display option
  • Multi-channel unit
  • Event log
  • Optional I/O
  • Modbus RTU communications
  • Profibus DP communications
  • DeviceNet communications
  • Ethernet (Modbus TCP) communications
  • EtherNet/IP communications
  • CC-Link communications
  • Profinet IO communications
  • Voltage, current and power control
  • Complete diagnostics
  • Energy counter
  • Single phase load tap changer

Specifications

Brand

Accuracy

  • Measurement Accuracy < 1 %

Alarm

  • Alarm Relay Configuration: Fuse Blown
  • Alarm Relay Configuration: Process Alarm

Ambient Temperature Range

  • Ambient Temperature Error: < 0.01 %/°C

Approvals & Certifications

  • CE
  • EN 60947-4-3 Emissions Class A
  • IEC 364
  • UL 508A Test

Calibration

  • Calibration Error: < 0.5 %

Communication

  • 10 BaseT IEEE 801
  • 2-Wire 485 Modbus (RJ45 Connector)
  • CC-Link
  • DeviceNet
  • EtherNet/IP
  • FOUNDATION Fieldbus
  • Modbus RTU
  • Modbus/TCP
  • PROFIBUS DPV1 (with D Typical Connector)
  • PROFINET IO

Configuration

  • Load Configuration: Single-Phase
  • Load Configuration: Star

Current

  • High Power Use: 1 mA
  • Short Circuit Current: < 24 mA
  • Short Circuit O/P Current: 15 mA - Max.

Display

  • 7 High x 5 Wide Yellow-Green Dot Matrix LCD
  • Remote Display

Dissipation

  • Power Dissipation: 1.3 W Per Amp Per Phase

Electrical Connectors

  • Removable 10-Way Connector (5.08 mm Pitch) Terminal Block
  • RJ45

Environmental Protection

  • IP10 (EN 60529)

Frequency

  • 47 to 63 Hz

Humidity

  • 5 to 95 % Relative Humidity, Non-Condensing

Input

  • Analog Input 1 & 2: 0-10 V
  • Analog Input 1 & 2: 0-20 mA
  • Total Current Working Input Span: -1 to 25 mA
  • Total Voltage Working Input Span: -0.25 to 12.5 V

Input Function

  • Analog
  • Analog Input 1 & 2 Function: Current Limit
  • Analog Input 1 & 2 Function: Current Transfer Span
  • Analog Input 1 & 2 Function: Power Limit
  • Analog Input 1 & 2 Function: Set Point Limit
  • Analog Input 1 & 2 Function: Voltage Limit
  • Digital Input 2 Function: Alarm Acknowledgement
  • Digital Input 2 Function: Remote Set Point Selection

Input Impedance

  • Digital I/O: 10 kiloohms

Insulation

  • Rated Insulation Voltage: 50-690 V

Length

  • Altitude, Max.

Linearity

  • Analog Output of Linearity Error: < ± 0.1 % of Full Scale
  • Linearity Error: ± 0.1 % of Full Scale

Load Resistance

  • Maximum
  • Minimum Load Resistance: > 800 ohms

Media

  • Atmosphere: Non-Conductive
  • Atmosphere: Non-Corrosive
  • Atmosphere: Non-Explosive

Operating Temperature

  • 0° to 50° C (32° to 122° F)

Output

  • 10 V ± 0.3 V at 5.5 mA
  • Analog Output of Total Current Working Span (within -0.3 V to 12.5 V Voltage Span): -24 to 24 mA
  • Analog Output: 0-10 V
  • Analog Output: 0-20 mA
  • DC Output Conductance: < 1 μA/V
  • Total Voltage Working Span [within ± 20 mA Typical Current Span]: -0.5 to 12.5 V

Output Function

  • Analog Output Function: Current
  • Analog Output Function: Impedance
  • Analog Output Function: Power
  • Analog Output Function: Voltage

Output Impedence

  • DC Output Impedance: < 2 ohms

Power Requirement

  • 60 W + Power Module Fans (15 W Each for 400 A/500 A/630 A Power Modules, 10 W Each for 160 A/250 A Modules)

Resistance

  • Digital I/O of Closed Contact (Active) Resistance: 500 ohms
  • Input Resistance (Negative Terminal to 0 V): 150 ohms
  • Input Resistance (Positive Terminal to 0 V): > 140 kiloohms

Resolution

  • Resolution (Noise Free): 13-bits

Response Time

  • Analog Output of Hardware Response Time (10 % to 90 %): 20 milliseconds
  • Digital I/O of Hardware Response Time: 100 μS
  • Hardware Response Time: 5 milliseconds

Shock

  • EN 60068-2-29: 10 G Peak, 6 milliseconds Duration, 100 Bumps

Storage Temperature

  • -25° to 70° C (-13° to 158° F)

Supply Voltage

  • ≤ 300 Vrms
  • 85-265 Vac

Thermal Drift

  • Ambient Temperature Drift: ± 0.012 %/°C Typical
  • Ambient Temperature Drift: ± 0.04 %/°C, Max.

Vibration

  • EN 60068-2-6: 1 G, 67 to 150 Hz

Voltage

  • Allowable Voltage (Negative Terminal to 0 V): ± 1 V
  • Analog Output of Open Circuit Voltage: 1 V
  • Rated Impulse Withstand Voltage (Uimp): 0.5-6 kV