Mini8 Controller

Brand: Eurotherm

The Mini8 Controller offers high performance control usually only found in Eurotherm panel mount PID controllers.

It is also a very competitive and compact data acquisition device.

Its modular design enables its I/O and feature set to be selected to cater for a wide range of applications from simple to complex.

The Mini8 controller is an ideal partner to a programmable logic controller.

Able to multi-drop on either serial, fieldbus or ethernet communications.

It offers an effective alternative to performing Analog measurement or loop control in a PLC.

Implementing these functions in the Mini8 controller PLC relieves it of the burden of performing Analog functions, often allowing a lower specification processor to be used.
Features
  • 16 Control loops
  • 32 Analog inputs
  • Modular and compact
  • SP programming
  • Maths and logic
  • Remote HMI
  • Modbus RTU
  • DeviceNet network
  • Profibus DP network
  • Modbus TCP
  • EtherNet/IP
  • EtherCAT
  • OEM Security

Specifications

Brand

Accuracy

  • Current-Transformer Input Card (Factory Set Accuracy): Better than ± 2 % of Range
  • Output Card (Setting Accuracy): ± 0.5 % of Reading
  • Thermocouple (CJ Accuracy): ± 1° C (± 1.8° F)
  • Thermocouple: ± 1° C (± 1.8° F) ± 0.1 % of Reading (Using Internal CJC)

Approvals & Certifications

  • CE
  • cUL Listed (File E57766)
  • EMC Directive 2004/108/EC, EN 61326
  • LVD Directive 73/23/EEC

Approvals & Certifications

  • EN 61010
  • FC (Factory Calibration Certificate)

Calibration

  • Input Card Pt100 (Calibration Error): ± 0.1 ohms ± 0.1 % of Reading, 22 to 420 ohms
  • Input Card Pt100 (Calibration Error): ± 0.3° C (± 0.54° F) ± 0.1 % of Reading, -200° to 850° C (-328° to 1,562° F)
  • Input Card Pt1000 (Calibration Error): ± 0.2° C (± 0.36° F) ± 0.1 % of Reading, -200° to 850° C (-328° to 1,562° F)
  • Input Card Pt1000 (Calibration Error): ± 0.8 ohms ± 0.1 % of Reading, 220 to 4,200 ohms

Communication

  • Baud Rate: 100Base-T
  • Baud Rate: 125K, 250K or 500K
  • Baud Rate: 4,800, 9,600, 19,200 bit/sec
  • DeviceNet: CAN, 5-Pin Standard Open Connector with Screw Terminals
  • EtherCAT: Standard Ethernet RJ45 Connector
  • EtherNet/IP: Standard Ethernet RJ45 Connector
  • Ethernet: Standard Ethernet RJ45 Connector
  • Modbus RTU: RS-485, 2 x RJ45, User Select Switch for 3-Wire or 5-Wire
  • Modbus/TCP
  • PROFIBUS DP: RS-485 Via Standard 9-Pin D Connector or 2 RJ45 Connectors

Consumption

  • Power Comsumption: 15 W, Max.

Current

  • Ananlogue Output (Output Current): 0-20 mA
  • Current-Transformer Input Card (Current Input): 0-50 mArms, 50/60 Hz Nominal
  • Fixed I/O Resources (Contact Current): < 1 A (Resistive Loads)
  • Fixed I/O Resources, Logic Input Card (Input Current): 10 mA - Max.
  • Fixed I/O Resources, Logic Input Card (Input Current): 2.5 mA Approximately at 10.8 V
  • Input Card (Pt100, Pt1000 Bulb Current): 300 μA
  • Relay Output Card, Max.
  • Thermocouple (Input Leakage Current): < 100 NA (1 NA Typical)

Humidity

  • Operating Humidity: 5 to 95 % Relative Humidity, Non-Condensing

Input

  • Current-Transformer Input Card (Input Load Burden): 1 W
  • Fixed I/O Resources, Logic Input Card: 24 Vdc
  • Thermocouple: -77 to 77 mV
  • Thermocouple8 8-Channel & Thermocouple4 4-ChanneL Thermocouple Input Card (Common Mode Rejection): > 120 dB, 47 to 63 Hz
  • Thermocouple8 8-Channel & Thermocouple4 4-ChanneL Thermocouple Input Card (Series Mode Rejection): > 60 dB 47 to 63 Hz

Interval Time

  • Load Failure Detection (Measurement Interval): 1 to 60 seconds

Isolation

  • Channel to Channel, Isolation to System: 42 V Peek, Max.
  • Relay Output Card (Channel to Channel, Isolation to System): 264 V, 230 V Nominal

Linearity

  • Input Card (Pt100, Pt1000 Linearity Error): ± 0.02 ohms, ± 0.05° C (± 0.09° F)

Load

  • Ananlogue Output: Max.

Mounting

  • DIN Rail to EN 50022 35 x 7.5 or 35 x 15 Horizontally
  • Horizontal

Operating Temperature

  • 0° to 55° C (32° to 131° F)

Output

  • Digital Output Card (Logic 0 Voltage Output): < 1.2 Vdc No-Load
  • Digital Output Card (Logic 0 Voltage Output): 0.9 V Typical
  • Digital Output Card (Logic 1 Current Output): 100 mA - Max.
  • Digital Output Card (Terminal Supply Protection): Card Supply is Protected by 200 mA Selfhealing Fuse
  • Output Card: 0-20 mA, 360 ohms Load, Max.
  • PID Control Loop Blocks (Control Output): Analog 4-20 mA
  • Relay Output Card (Min. Contact Wetting): 10 mA
  • Relay Output Card (Min. Contact Wetting): 5 Vdc
  • Relay Output Card, Max.

Power Supply

  • 24 Vdc

Resistance

  • Input Card (Pt100, Pt1000 Lead Resistance): 22 ohms, Max.
  • Input Card Pt100 (Input Range): 0 to 420 ohms, -242.02° to 850° C (-403.64° to 1,562° F)
  • Input Card Pt100 (Measurement Noise): 0.016 ohms, 0.04° C (32.07° F) Peak-to-Peak, 1.6 seconds Channel Filter
  • Input Card Pt100 (Measurement Noise): 0.06 ohms, 0.15° C (32.27° F) Peak-to-Peak, No Filter
  • Input Card Pt1000 (Input Range): 0 to 4,200 ohms, -242.02° to 850° C (-403.6° to 1,562° F)
  • Input Card Pt1000 (Measurement Noise): 0.2 ohms, 0.05° C (32.09° F) Peak-to-Peak, 1.6 seconds Channel Filter
  • Input Card Pt1000 (Measurement Noise): 0.6 ohms, 0.15° C (32.27° F) Peak-to-Peak, No Filter
  • Thermocouple (Input Resistance): > 100 megaohms

Resolution

  • Analog Output Card: 1 μA Typical
  • Input Card Pt100: 0.008 ohms, 0.02° C (32.04° F)
  • Input Card Pt1000: 0.6 ohms, 0.15° C (32.3° F)
  • Thermocouple: 1.6 µV with 1.6 seconds Filter Time
  • Thermocouple: 20-bit (∑∆ Converter)

RTD Type

  • Pt100
  • Pt1000

Sensor, Probe Type

  • B Thermocouple
  • C Thermocouple
  • J Thermocouple
  • K Thermocouple
  • L Thermocouple
  • N Thermocouple
  • R Thermocouple
  • S Thermocouple
  • T Thermocouple

Storage Temperature

  • -10° to 70° C (14° to 158° F)

Supply Voltage

  • Digital Output Card (Channel Supply): 15-30 Vdc
  • Power Supply Voltage: 17.8-28.8 Vdc

Temperature Coefficient

  • Input Card (Pt100, Pt1000): ± 0.002 % ohms Reading/°C Ambient Change Relative to Normal Ambient 25° C (77° F)
  • Thermocouple: < ± 50 ppm (0.005 %) of Reading/°C

Temperature Range

  • Thermocouple (Cold Junction Range): -10° to 70° C (14° to 158° F)

Unit of Measure

  • Temperature Unit: Centigrade
  • Temperature Unit: Fahrenheit

Voltage

  • Fixed I/O Resources (Terminal Voltage): < 42 Peek

Documentation

show more