3216L Temperature/Process Controller
Brand: EurothermThe entry level 3216L controller offers precision control of temperature and other process variables in an affordable format.
The emphasis is on simplicity and ease of use.
A simple 'Quick Start' code is used to configure all the functions essential for controlling your process.
This includes input sensor type, measurement range, control options and alarms, making 'Out of the Box' operation truly achievable.
PID with autotune is available as standard with control outputs allowing relay and logic SSR drive in heat only or heat/cool configurations.
Up to two latching alarm trip relays are available.
Features- Entry level Eurotherm controller
- IP65 sealing and washdown membrane front
- Plastic extrusion
- Packaging machines
- Food and Beverage applications
- Overtemperature protection
- Process alarms
Specifications
Brand
Accuracy
- Calibration Accuracy: < ± 0.25 % of Reading ± 1 LSD
- Cold Junction Accuracy: < ± 1° C (1.8° F) at 25° C (77° F) Ambient
- Linearisation Accuracy: < 0.1 % of Reading
Applications
- Food & Beverage
Approvals & Certifications
- CE
- cUL Listed (File E57766)
- EMC Emissions & Immunity: BS EN 61326
- GOST
Control Functions Characteristics
- PID Control
Display
- LCD TN with Backlight Display
- Lower Display Status Beacons: 5-Character Starburst, Green Units
- Main PV Display: 4-Digit, Green
Electrical Connectors
- Form A
Electrical Contacts
- Changeover Contact
- Normally Open
Electrical Rating
- AA Relay, Relay Output: 2 A at 264 Vac
- AA Relay, Relay Output: Min. 100 mA at 12 Vdc
- Logic Output: OFF < 300 mV at 100 μA
- Logic Output: ON 12 Vdc at < 44 mA
Environmental Protection
- IP65
- IP66
- NEMA 4X
Function
- Alarm
- Control Outputs
Humidity
- Operation & Storage: 5 to 90 % Relative Humidity, Non-Condensing
Input
- Digital Input of Contact Closure: Closed 500 ohms
- Linear Process Input: 0-10 V with 100 kiloohms / 806 ohms External Divider Module
- Linear Process Input: -10 to 80 mV
Input Impedance
- 100 megaohms
Isolation
- 264 Vac Double Insulation from the PSU
Mounting
- Panel Mount: 1/16 DIN
Operating Temperature
- 0° to 55° C (32° to 131° F)
Power Requirement
- 100-240 Vac, (-15 %, 10 %)
- 48 to 62 Hz, Max.
Resolution
- 17-bits
RTD Type
- 3-Wire Pt100 DIN 43760
Sample Rate
- 4 Hz (250 milliseconds)
Sensor, Probe Type
- B Thermocouple
- J Thermocouple
- K Thermocouple
- L Thermocouple
- N Thermocouple
- R Thermocouple
- S Thermocouple
- T Thermocouple
Shock
- BS EN 61010
Storage Temperature
- -10° to 70° C (14° to 158° F)
Thermal Drift
- < 50 ppm Typical
Update Time
- Software Loop Update: 250 milliseconds
Vibration
- 2 G Peak, 10 to 150 Hz
Voltage
- The Rated Impulse Voltage for Equipment on Nominal 230 V Mains is 2,500 V