400 Series Type J402K Models 455 to 559 Differential Pressure Switch
Brand: United Electric Controls LtdThe 400 Series is a versatile family of vacuum, pressure, differential pressure and temperature switches for applications that require single or multiple switching capabilities.
Dual and triple switch versions provide multi-output for alarm and shutdown, pre-alarm and alarm, high/low limit or level staging functions.
A wide variety of microswitch and process connection options, along with a weather-tight enclosure, make the 400 Series an ideal choice for most ordinary location applications. Its worldwide use is assured with approvals and certifications to agency standards.
Widely used throughout the process industries, the 400 Series provides threshold protection and control for many critical functions.
Typical installations are found in industrial gas production, energy generation including pumps, turbines and compressors, pulp and paper, and water and wastewater treatment.
Features- Epoxy-coated enclosure designed to meet enclosure Type 4X
- Wide variety of pressure sensors and materials
- Setting via reference dial or hex screw adjustment
- FM Approved
Specifications
Accuracy
- Differential Pressure Indication: Approximately 1.5 % Mid 50 % of Range, 3 % at Ends, Window is Plexiglass & Gasketed, Indicator may be Field Adjusted for Approximately ± 1 % Accuracy at any Set Point within Range
Adjustment Type
- Captive Clamp Screws
- Factory Set (Pre-Set)
- Set Point Adjustment
Ambient Temperature Range
- -40° to 71° C (-40° to 160° F), Set Point Typically Shifts less than 1 % of Range for a 28° C (50° F) Ambient Temperature Change
Applications
- Energy Generation Including Pumps
- Industrial Gas Production
- Pulp & Paper
- Turbines & Compressors
- Water & Wastewater Treatment
Approvals & Certifications
- ATEX Directive (94/9/EC) II 1 G EEx ia IIC T6 Tamb: -50° to 60° C (-58° to 140° F)
- CE
- CPT
- CSA C22.2 No. 14, File # E42272
- FM Class 3545
- GOST-R 51330.0, 51330.1, 51330.10 & 51330.14
- Low Voltage Directive (LVD) 2006/95/EC
- PED: 97/23/EC
- UL (C,US) 508
Approvals & Certifications
- ISO 9001
Deadband
- Inches WC: 1 to 4
- psi: 0.07 to 2 (kPa: 0.5 to 13.8, Mbar: 4.8 to 137.9)
Diaphragm Material
- Buna-N
- Teflon
Electrical Connectors
- 3/4” NPT
- 7/8” Diameter Knockout
- 7/8” Hole to 1/2” NPT Female Watertight Conduit Fitting
- Screw Terminal
Electrical Contacts
- Gold
- Normally Closed
- Normally Open
Electrical Rating
- 10 A at 125 Vdc Resistive, Deadband & Min. Set Point Will Increase
- 20 A, 125/250/480 Vac Resistive
- Adjustable Deadband, External Manual Reset, High Ambient, 15 A at 125/250/480 Vac Resistive, Temperatures up to 145° C (250° F)
- Close Deadband, 5 A at 125/250 Vac Resistive
- Vapor Sealed, Fungus Resistant Case,15 A 125/250 Vac Resistive
Enclosure Finish
- Epoxy Powder-Coated
Enclosure, Body Material
- Gasketed Die Cast Aluminum
Environmental Protection
- Intrinsically Safe
- IP66
- NEMA 4
- NEMA 4X
- Weathertight
Mounting
- Hole
- Pipe
- Surface
Name Plate, Tag Material
- Stainless Steel
NPT Connection
- 1/4” NPT Female
- 3/4” NPT Female
O-Ring Material
- Buna-N
Operating Pressure
- psi: -14.7 to 225 (kPa: -101.4 to 1,551, bar: -1 to 15.5)
Process Connection Material
- Aluminum
Proof Pressure
- psi: 225 (kPa: 1,551, bar: 15.5)
Repeatability
- Set Point Repeatability: ± 2 % of Full Scale
Set Point - Decreasing
- bar: 0.01 to 6.9
- Inches WC: 5 to 80
- kPa: 1.4 to 689.5
- psi: 2 to 100
Set Point - Increasing
- bar: 0.01 to 6.9
- Inches WC: 5 to 80
- kPa: 1.4 to 689.5
- psi: 2 to 100
Shock
- Set Point Repeats after 15 G, 10 millisecond Duration
Storage Temperature
- -54° to 71° C (-65° to 160° F)
Switch Type
- DPDT
- Two SPDT Switch, may be separated up to 100 % of Range
System Pressure
- bar: -1 to 15.5
- kPa: -101.4 to 1,551
- psi: -14.7 to 225
Vibration
- Set Point Repeats after 2.5 G, 5 to 500 Hz