Price
$582.00
CAD
Stock
50+ In Stock
- Input Voltage - 400 V, 50/60 Hz
- HP Rating - 1/2 HP
- Enclosure Type - IP20/Open
- RFI Filter - Only A2 RFI Filter
- Brake Chopper - No Factory Installed Brake Chopper
- Conformal Coating - No Conformal Coatings
- Version - 1st Version
Specifications
Brand
Environmental Conditions
Enclosures
- IP20 Chassis
- IP00 Chassis
- IP21
- IP55
- IP54
- IP66
Installation Location
- For use at altitudes of 1000 m or Less without derating
Storage Temperature
- -25° to 65° C
Ambient Temperature
- -10° to +50° C for above 45° C, there will be derating: please consult GE
Ambient Humidity
- 5 to 95 % Relative Humidity, Non-Condensing
Vibration
- 1.0 G
Cooling Method
- Fan Cooled all ratings. Fan Control auto, 50 % level, 75 % level, 100 % level Adjustable
Standards
Approvals & Certifications
- CE
- UL
- cUL
- C-Tick
- Suitable for use on a Circuit capable of delivering not more than 100,000 RMS symmetrical amperes for 230 V and 400 V.
Input Power Supply
Rated Input AC Voltage
- 200-240 Vac, 3-Phase, 50/60 Hz, ± 10 % V
- 380-480 Vac, 3-Phase, 50/60 Hz, ± 10 % V
- 525-690 Vac, 3-Phase, 50/60 Hz, ± 10 % V
Maximum Voltage Imbalance
- 3 % of rated Supply Voltage
True Power Factor
- > 0.9 at Rated Load
Displacement Power Factor
- > 0.98
Switching on Input Power Supply
- Maximum twice/minute up to 7.5 kW
- Maximum once/minute above 7.5 kW
Environment According to EN60664-1
- Overvoltage Category III/Pollution Degree 2
Output
Rated Output Voltage
- 0 to 100 % of Supply Voltage
Output Frequency
- 0 to 590 Hz
Switching on Output
- Unlimited
Acceleration / Deceleration Time
- 0.01-3600 seconds
Overload Current Rating
- Sinusoidal PWM Control (V/Hz, Avd. vector Control, Sensorless vector, and fl ux vector with motor feedback)
Control
Starting Torque
- 110 % Starting torque for 1 minute (Variable torque)
- 160 % Starting torque for 1 minute (Constant torque)
Carrier Frequency (Motor Noise, KHz)
- 1.5
- 2
- 2.5
- 3
- 3.5
- 4
- 5
- 6
- 7
- 8
- 10
- 12
- 14
- 1
- 16
Torque Boost
- Selectable by up to 5 individual V/Hz settings in V/Hz Mode or by 0 - 300 % setting of torque boost Parameter in Adv. vector mode
Acceleration / Deceleration Time
- 0.01-3600 seconds (4 acceleration and deceleration times are selectable via digital inputs. Acceleration and deceleration patterns can be selected from linear or deceleration patterns can be selected from linear or S-Curve)
Data Protection
- Passw Protection for quick menu or main menu, 0-9999.
Pattern Operation
- Settings via built-in logic Controller sequencer
Jump Frequency Control
- 4 jump (or skip) frequencies via Parameter set to avoid mechanical vibration
Slip Compensation
- Maintains motor at constant speed with load fluctuations
Torque Limit Control
- Output torque can be controlled within a Range of 0.0 to 160 % (0.1 and steps)
Preset Speeds
- 8 Programmable preset speeds selectable by 3 digital inputs
Trim Reference Setting
- Available for speed reference offset via potentiometer, Voltage Input, or Current Input
DC Injection Braking
- Starting frequency: 0.0-590 Hz
- Braking Time: 0.0-60.0 seconds
- Braking level: 0-100 % of rated Current
Jogging Operation
- Operation via on Key or Digital Input (Forward or Reverse)
Auto-Restart After Power Failure
- Restarts the drive without stopping after instantaneous Power failure
Energy Savings
- Controls output voltage to minimize motor loss during constant speed operation
Start Mode Function
- This functionality smoothly catches a Spinning motor
Logic Controller (LC)
Logic Controller Events
- Up to 37 Types of Programmable events
Comparators
- Array of 6 comparators
Timers
- Array of 8 timers, Adjustable from 0.0 to 3600 sec
Logic Rules
- Array of 6 boolean logic rules
Logic Controller States
- Array of 20 logic Controller action States
Process Controller (PID)
Feedback Select
- Resolver Option Module
- Encoder Option Module
- Motor Feedback
- No Function
- Separate Encoder
Anti Windup
- Enabled
- Disabled
Start Speed
- 0.0-200 Hz
Proportional Gain
- 0.00-10.00
Integral Time
- 0.1 - 10000.0 millisecond
Differential Time
- 0.0 - 10 s
Differential Gain
- 1.0-50.00
Feed Forward Factor
- 0 to 500 %
On Reference Bandwidth
- 0 to 200 %
Operation
Operation Method
- USB Port for Programming drive with optional PC Software
- Built-In RS-485 Modbud
- Jog Timer Operation: Stop after predetermined time frame
- Auto Digital Input: Proframmable for Start/stop, forward/reverse
- Keypad Operation: Hand Off
Frequency Reference Signal
- 0/4-20 mA Analog Input
- 0-10 Vdc Analog Input
- Speed Potentiometer: 0 to +10 Vdc, 10 to 0 Vdc
- Left or right arrow Buttons on keypad in manual mode
References
- frequency Input #1 or #2, network, or potentiometer
- Up to 3 Input references can be selected from analog Input #1 or #2
Input Signals
- 2x analog Inputs -10 to +10 V scalable or 0/4-20 mA scalable
- 2x pulse Inputs rated to 110 kHz or 1x pulse Input and 1 - encoder Input 24 Vdc rated to 4096 PPR
- 1x safe stop Digital Input suitable for category 3 installations to meet EN-954-1
- 6x Digital Inputs, 24 Vdc PNP or NPN
Output Signals
- 1x analog output 0/4-20 mA
- 2x Digital Outputs 24 Vdc (Digital outputs are used in place of 2 of the digital inputs)
- 2x form C Relays rated to 2A at 230 Vac
Keypad
Protective Functions
- DC Link Voltage High
- Brake Check
- Brake Chopper Short Circuited
- Brake Resistor Short Circuited
- Control Word Timeout
- Short Circuit
- DC Link Voltage Low
- Ground Fault
- Torque Limit
- Motor Thermistor Overtemperature
- Motor Overtemperature
- Drive Overload
- DC Undervoltage
- DC Overvoltage
- Overcurrent
- Internal Fan Fault
- External Fan Fault
- Power Board Overtemperature
- Serial Comms Bus Fault
- Auto Tuning Fault
- Soft Charge Fault
- No Motor
- Keypad Error
- Drive Initialzied to Defualt Value
- Mechanical Brake Low
- Current Limit
- Auto Tune Low Inom - Motor Current is Too Low
- Auto Tune Check - Wrong Motor Parameters
- Control Voltage Fault
- Internal Fault
- Missing W Phase
- Missing V Phase
- Missing U Phase
- Line Phase Loss
- Hardware Mismatch
- Speed Limit
Keypad Features
- LCd Display with 6 Alpha-numberic Lines
- LED Amber (Active Menu Keys)
- LED Red (Alarm)
- LED Yellow (Warning)
- LED Green (ON)
- IP65 Rating when Remote Mounted on Enclosure
- Copycat Feature
- Remote Mount Option
- Hot Pluggable
- Multi-language Support
Password
- 2 Level Password Protection
Alternate Motor Parameters
- Up to 4 separate complete Parameter set-Ups are available
Graphical Trending
- Trend speed, Power, frequency or any value Programmed in Status display
RS-485 Modbus RTU Serial Communications
Physical Level
- EIA/RS-485
Transmission Distance
- 500 m
Node Address
- 32
Transmission Speed (bits/s)
- 115200
- 38400
- 19200
- 9600
- 4800
- 2400
Transmission Mode
- Half Duplex
Transmission Protocol
- Modbus RTU
Character Code
- Binary
Character Length
- 8-bits
Error Check
- CRC
Mounting Clearance
- All AF-650 GP drives can be Mounted side-by-side without Spacing
- For all drives rated 75 kW or below Allow 100 mm free Space above and below
- For all drives rated 90 kW and above Allow 225 mm free Space above and below