Enclosures
- IP20 Chassis
- IP54
- IP55
- IP21
- IP00 Chassis
Installation Location
- For use at altitudes of 1000 m or Less without derating.
Ambient Temperature
- 10° to +50° C for above 45° C, there will be derating
Ambient Humidity
- 5 to 95 % Relative Humidity, Non-Condensing
Cooling Method
- Fan Cooled all ratings. Fan Control auto, 50 % level, 75 % level, 100 % level Adjustable
Approvals & Certifications
- Suitable for use on a Circuit capable of delivering not more than 100,000 RMS symmetrical amperes for 230 V and 400 V.
- C-Tick
- cUL
- UL
- CE
Rated Input AC Voltage
- 525-690 Vac, 3-Phase, 50/60 Hz, ± 10 % V
- 380-480 Vac, 3-Phase, 50/60 Hz, ± 10 % V
- 200-240 Vac, 3-Phase, 50/60 Hz, ± 10 % V
Maximum Voltage Imbalance
- 3 % of rated Supply Voltage
True Power Factor
- > 0.9 Nominal at Rated Load
Displacement Power Factor
Switching on Input Power Supply
- Maximum twice/minute up to 7.5 kW
- Maximum once/minute above 7.5 kW
Environment According to EN60664-1
- Overvoltage Category III/Pollution Degree 2
DC Link Reactors
- Built-In DC Link Reactors on all ratings
RFI Filters
- Built-In RFI Filters to reduce noise generated by the drive
Rated Output Voltage
- 0 to 100 % of Supply Voltage
Acceleration / Deceleration Time
Control Method
- Sinusoidal PWM Control (V/Hz, Avd. vector Control)
Starting Torque
- 110 % Starting torque for 1 minute (Variable torque)
Carrier Frequency (Motor Noise, KHz)
- 16
- 14
- 12
- 10
- 8
- 7
- 6
- 5
- 4
- 3.5
- 3
- 2
- 1.5
- 1
- 2.5
Torque Boost
- 0 to 300 % setting to compensate voltage in relation to the load at low speed
Acceleration / Deceleration Time
- 0.01-3600 seconds (4 acceleration and deceleration times are selectable via digital inputs. Acceleration and deceleration patterns can be selected from linear or S-Curve)
Data Protection
- Password Protection for quick menu or main menu, 0-9999
Pattern Operation
- Settings via built-in logic Controller sequencer
Jump Frequency Control
- 4 jump (or skip) frequencies via Parameter set to avoid mechanical vibration
Slip Compensation
- Maintains motor at constant speed with load fluctuations
Torque Limit Control
- Output torque can be controlled within a Range of 0.0 to 110 % (0.1 and steps)
Preset Speeds
- 8 Programmable preset speeds selectable by 3 digital inputs
Built-In Communications
- Apogee FLN P1
- Metasys N2
- Modbus RTU
- Drive RS-485
Trim Reference Setting
- Available for speed reference offset via potentiometer, Voltage Input, or Current Input
DC Injection Braking
- Braking level: 0-100 % of rated Current
- Braking Time: 0.0-60.0 seconds
- Starting frequency: 0.0-590 Hz
Auto-Restart After Power Failure
- Restarts the drive without stopping after instantaneous Power failure
Jogging Operation
- Operation via on Key or Digital Input (Forward or Reverse)
Energy Savings
- Controls output voltage to minimize motor loss during constant speed operation
Start Mode Function
- This functionality smoothly catches a Spinning motor
Fire Override Mode
- Overrides drive’s Protective features and keeps motor running
Pump Cascade Controller
- Distributes running hours evenly over up to 4 pumps
Sleep Mode
- Drive detects Low or no fl ow conditions and Adjusts output
Dry Pump Detection
- Detects pump Operation and can set off Alarm, shuts off, or other Programmed actions
Belt Monitoring
- Drive can detect Relationship between Current and speed to recognize a broken belt
Real Time Clock
- With Programmable timed actions
Logic Controller (LC) Sequencer
Logic Controller Events
- Up to 38 Programmable events
Timers
- Array of 8 timers, Adjustable from 0.0 to 3600 sec
Logic Rules
- Array of 6 boolean logic rules
Logic Controller States
- Array of 20 logic Controller action States
Controller
- 4 Auto Tune PID Controllers Built-in
Feedback Select
- Up to 2 references. Selectable - no function, motor feedback, separate encoder, encoder option module, or resolver option module
Integral Time
- 0.1 - 10000.0 millisecond
Operation Method
- Communications: RS-485 Modbus RTU, Metasys N2, and Apogee FLN P1 USB Port for Programming drive with optional PC Software
- Keypad Operation: Hand, off, auto Digital Input: Programmable for Start/stop, forward/reverse, jog timer Operation: Stop after predetermined time frame
Frequency Reference Signal
- 0/4-20 mA Analog Input
- 0-10 Vdc Analog Input
- Speed Potentiometer: 0 to +10 Vdc, 10 to 0 Vdc
- Left or right arrow Buttons on keypad in manual mode
References
- Up to 3 Input references can be selected from analogue Input #1 or #2, frequency Input #1 or #2, network, or potentiometer
Output Signals
- 2x Digital Outputs 24 Vdc (Digital outputs are used in place of 2 of the digital inputs)
- 2x form C Relays rated to 2A at 230 Vac
- 1x analog output 0/4-20 mA
Protective Functions
- Line Phase Loss
- Serial Comms Bus Fault
- Hardware Mismatch
- Speed Limit
- Auto Tuning Fault
- Soft Charge Fault
- No Motor
- Keypad Error
- DC Overvoltage
- DC Undervoltage
- Drive Overload
- Motor Overtemperature
- Motor Thermistor Overtemperature
- Torque Limit
- Overcurrent
- Ground Fault
- Short Circuit
- Control Word Timeout
- Brake Resistor Short-CCircuited
- Brake Chopper Short-Circuited
- Brake Check
- DC Link Voltage High
- Internal Fan Fault
- External Fan Fault
- Power Board Overtemperature
- Missing U Phase
- Missing V Phase
- Missing W Phase
- Internal Fault
- Control Votlage Fault
- Auto Tune Check - Wrong Motor Parameters
- Auto Tune Low Onom - Motor Current is too Low
- Current Limit
- Mechanical Brake Low
- Drive Initialized to Default Value
- DC Link Voltage Low
Keypad Features
- LCD display with 6 alpha-numeric lines
- Multi-language support
- Hot pluggable, remote Mount option, and copycat Feature, IP65 rating when remote Mounted on Enclosure
- LED’s - Green - drive is on, Yellow - indicates a warning, Red - indicates an Alarm, amber - indicates active menu keys and H-O-A keys
Password
- 2 level password Protection
Alternate Motor Parameters
- Up to 4 separate complete Parameter set-Ups are available
Graphical Trending
- Trend Speed
- Power
- Frequency
RS-485 Modbus RTU Serial Communications
Transmission Speed
- 2400
- 4800
- 9600
- 19200
- 38400
- 115200
Mounting Clearance
- All AF-600 FP drives can be Mounted
- side-by-side without Spacing. for all drives rated 90 kW or below Allow 100 mm free Space above and below
- For all drives rated 110 kW and above Allow 225 mm free Space above and below