AP4570 Track-Hold & Peak-Hold Process Function
Brand: EurothermThe AP4570 offers two modes of operation - Track and Hold and Track and Peak-Hold. In "Track and Hold" operation the output tracks the input signal. When an external contact is closed, the input level is "saved" and its corresponding output signal is held indefinitely until the contact is opened. Releasing the hold switch (pins 8 and 11) allows the output to again follow the input.
The "Track and PeakHold" mode is similar to "Track and Hold" operation except upon contact closure (pins 8 and 11) the highest input is "saved" and the corresponding output is held until a higher signal level occurs.
Displaying prices & availability for Ohio, United States in CAD. Change location.
Models matching criteria: 1
- Input Range - 0-1V
- Output Range - 0-1V
- Optional Configuration - Canadian Standards Association Certification
- Line Power - 120 VAC Standard
50+ In Stock
$1,088.00
CAD
Does not ship to OH, United States
Specifications
Brand
Applications
- Low-Cost Sample & Hold
- Peak Detection
Approvals & Certifications
- CSA
Consumption
- Power Consumption: 3 W Typical
- Power Consumption: 5 W, Max.
Electrical Connectors
- 11-Pin
- Screw Terminal
Enclosure Finish
- Urethane Coating
Input
- 0-10 V
- 1 A, Max.
- 200 V, Max.
- 4-50 mA
Input Impedance
- Current Input: 20 ohms
- Voltage Input: > 200 kiloohms
Linearity
- ± 0.05 % of Span Typical
Mounting
- DIN Rail
- Track/Surface
Operating Temperature
- 0° to 60° C (32° to 140° F)
Output
- 0-10 V
- 10 V, Max.
- 4-50 mA
- 50 mA - Max.
- Current: 15 V Compliance at 20 mA (750 ohms, Max.
- Output Ripple: 0.25 % of, Max.
- Voltage: 10 mA - Max.
Output Impedence
- Current Output: > 100 kiloohms
- Voltage Output: < 10 ohms
Power
- 120 Vac (± 10 %, 50-400 Hz)
- Available: 240 Vac (± 10 %, 50-400 Hz)
Response Time
- 100 milliseconds Typical
Stability
- 15 Minute Warm-Up: ± 0.02 %/°C Typical
Storage Temperature
- -20° to 85° C (-4° to 185° F)
Voltage
- Common Mode Voltage: 600 Vdc or Peak AC, Max.