E-Rated Series - Medium Voltage Fuses
Brand: Littelfuse, IncE-rated fuses have time current characteristics designed to provide current-limiting protection for power transformers, potential transformers, power centers, feeder centers, and unit sub stations.
When properly applied, they can protect against high and low fault currents.
NEMA Standards for E-rated medium voltage fuses require that fuses rated 100E or less open within 300 seconds (5 minutes) when subjected to an RMS value of 200-240% of the fuse continuous current rating; and fuses with an E rating larger than 100E must open within 600 seconds (10 minutes) when subjected to an RMS current of 220- 240% of the fuse’s continuous current rating.
These values establish one point on the time-current curve.
Features- Hermetically sealed for use in hazardous locations (add 'S' suffix to part number)
- Clip-lock (CL) available
- Live parts and mounting clips are available for mounting E-rated single, double, and triple barrel fuses. Note, all clips are sold in pairs.
- Power Transformer Protection
- Potential Transformer Protection
- Motor Controller Back-up Protection
- Fused Switches
- Feeder Circuits
Documentation
Data Sheets
2D Prints
Technical Papers
Time Current Curves
- E-Rated Time Current Curves - 15.5kV E-Rated 100E-300E - Clearing Time pdf 581 KB
- E-Rated Time Current Curves - 15.5kV E-Rated 100E-300E - Melting Time pdf 581 KB
- E-Rated Time Current Curves - 15.kV E-Rated 10E-80E - Clearing Time pdf 577 KB
- E-Rated Time Current Curves - 2.75kV E-Rated 100E-400E - Clearing Time pdf 596 KB
- E-Rated Time Current Curves - 2.75kV E-Rated 100E-400E - Melting Time pdf 598 KB
- E-Rated Time Current Curves - 2.75kV E-Rated 10E-80E - Clearing Time pdf 587 KB
- E-Rated Time Current Curves - 2.75kV E-Rated 10E-80E - Melting Time pdf 581 KB
- E-Rated Time Current Curves - 25.8kV E-Rated 15E-100E - Clearing Time pdf 588 KB
- E-Rated Time Current Curves - 25.8kV E-Rated 15E-100E - Melting Time pdf 583 KB
- E-Rated Time Current Curves - 25.8kV E-Rated 15E-100E - Melting Time pdf 576 KB
- E-Rated Time Current Curves - 38.0kV E-Rated 15E-80E - Clearing Time pdf 572 KB
- E-Rated Time Current Curves - 38.0kV E-Rated 15E-80E - Melting Time pdf 566 KB
- E-Rated Time Current Curves - 5.5kV E-Rated 10E-600E - Clearing Time pdf 1.4 MB
- E-Rated Time Current Curves - 5.5kV E-Rated 10E-600E - Melting Time pdf 1.5 MB
- E-Rated Time Current Curves - 8.25.kV E-Rated 10E-80E - Melting Time pdf 581 KB
- E-Rated Time Current Curves - 8.25kV E-Rated 10E-80E - Clearing Time pdf 582 KB
- E-Rated Time Current Curves 8.25 kV E-Rated 100E-400E Clearing Time pdf 292 KB
- E-Rated Time Current Curves 8.25 kV E-Rated 100E-400E Melting Time pdf 292 KB